Model | Cat. # | Description | List Price | Quantity/Status | Distributor Stock Check |
---|---|---|---|---|---|
2137.90 | 2137.90 | Adapter - 600 V CAT III Power to Phase Adapter for use with Models PEL 102 & PEL 103 | $379.00 |
|
|
|
Electrical Characteristics | |||||
Range of use | Phase-to-neutral voltage: (100 to 346) VAC Phase-to-phase voltage: (100 to 600) VAC |
||||
Max. input voltage | Permanent: +10% (660 VAC) Transient: +15% (690 VAC) |
||||
Min. input voltage | 85 VAC (-15%) | ||||
Max. output voltage | 360 Vpeak | ||||
Frequency | (50, 60 and 400) Hz | ||||
Consumption | 100 VA max at (50, 60, and 400)Hz | ||||
Environmental conditions | |||||
Reference range: | (73 to 37) °F (23 ± 3) °C and (45 to 75) % RH | ||||
Operation range: | (32 to 122 ) °F (0 to 50) °C and (10 to 85) % RH | ||||
Storage range: | (-4 to 158) °F (-20 to +70) °C and (0 to 95) % RH | ||||
Indoor use: | Level of pollution: 2; IEC 61010-1 600 V CAT III | ||||
Altitude: | < 2,000 m | ||||
Storage: | < 10,000 m | ||||
Characteristics of construction | |||||
Dimensions (L x H x D): | (5 x 3.8 x 1.5) in (121 x 97 x 39) mm | ||||
Mass: | ~7oz (200 g) | ||||
Spiral cord: | ~11 in (30 cm) | ||||
Ingress protection: | IP 40 per IEC 60529 except for the terminals (IP 20) IK 04 per IEC 50102 |
||||
Drop Test: | 1 metre per IEC 61010-1 | ||||
Electromagnetic compatibility | |||||
Dimensions (L x H x D): | Emissions and immunity in an industrial setting compliant with IEC 61326-1 |